ZW32 series Breakers are used in distribution systems. Circuit breakers are used to make and break normal and fault currents. Breakers are fully equipped with sensors and a controller to provide a means of protection and control. In case of a line fault, breakers can break and make currents several times, thus avoiding longer network interruptions due to temporary faults. The manufacture, design, and testing of the vacuum recloser is based on current standards IEC 62271-100.
Application of 11KV Outdoor Circuit Breaker
The vacuum circuit breaker is equipped with one integrated current transformer per pole. The current transformer has a ratio of 600 A:5 A. It is for protection purposes and optimized for operation with the controller.
Technical parameters of 11KV Vacuum Circuit Breaker
Products Type
|
ZW32-12
|
Maximum System Voltage
|
12kV
|
Rated Continuous Current
|
630A
|
Rated Frequency
|
50/60Hz
|
Short Time Withstand Current
|
20kA/1sec
|
Mainly Active Load Current
|
630A
|
Number of Load-break Operations
|
30
|
Short-circuit Making Current (peak)
|
50kA
|
Number of Making Operations
|
5 times
|
Cable Charging Current
|
25A
|
Line Charging Current
|
1.5A
|
Closed Loop Circuit Current
|
630A
|
Transformer Magnetizing Current
|
22A
|
Wet Condition-10sec Ph- Ph-Eth, Across Interrupters
|
45kV
|
DryCondition-1min,Ph- Ph, Phase to Earth
|
42kV
|
Dry Condition - 1 min AcrossInterrupter
|
48kV
|
Phase to Phase, Phase to Earth
|
75kV
|
Across Interrupter
|
85kV
|
Internal Arc Test
|
20kA /0.1 sec
|
Arc Extinction Medium
|
vacuum
|
Insulation Medium
|
vacuum
|
Creepage Distance (Silicon)
|
780mm
|
Dry arcing distance
|
≥200mm
|
IP Level
|
67
|
Closing/Opening Time
|
<1sec
|
Mechanical Operations (Guaranteed)
|
10000times
|
Operating Temperature (*Manual Type)
|
-25~+70℃
|